Seitenansicht 40
8624-2 Standard - 39
english
7 ERROR MESSAGES
Display Cause Remedy
ERR0
Standard signal at transmitter Check standard signal of trans-
input lies outside range mitter or its connection to controller
(4 - 20 mA, 0 - 10 V)
ERR1
Standard signal of external Check standard signal
setpoint lies outside range
(4 - 20 mA, 0 - 10 V)
ERR2
Controller output to proportional Increase the pressure in order to
valve is > 95% reach the required setpoint with
the proportional valve selected
ERR9
Only in mode
SENS
with Set the lower limit for the valve drive
S LO
S HI
or correctly value (see 6.6.9.
VALV
)
EXLO
EXHI
Set the lower limit for valve drive
correctly (see 6.6.9
VALV
)
Actual value too great (can no
longer be compensated) or in
manual mode, the valve
cannot be closed