10
42 UINT8 Remote / local switching
0: local
1: remote
43 UINT16 Alteration 1
The contents of the following indices can be automatically
altered by the internal processor; i.e. meaningless user
parametrations will be automatically corrected.
Index Bit Index Bit
57 0 81 6
56 1 92 7
85 2 91 8
84 3 101 9
58 4 125 10
82 5 170 11
44 UINT16 Alteration 2
The contents of the following indices can be automatically
altered by the internal processor; i.e. meaningless user
parametrations will be automatically corrected.
Index Bit Index Bit
61 0 171 5
63 1 76 6
66 2 166 7
145 3 181 8
156 4
45 UINT8 Address / station address of the unit
49 UINT8 PT 100 Type (connection type)
0: 3 conductors
1: 4 conductors
50 UINT16 Mask configuration 1st input
51 UINT8 Type 1st input
0: 0 - 10 V
1: 0 - 20 mA
2: 4 -2 0 mA
3: frequency
4: Pt 100
5: thermocouple J
6: thermocouple K
7: thermocouple T
8: thermocouple R
9: thermocouple S
Kommentare zu diesen Handbüchern