1Operating InstructionsInterface RS 232 andInterface RS 485 / ProfibusforDigital Industrial Controller Type 1110andDigital Batch Controller Type 1115
1042 UINT8 Remote / local switching0: local1: remote43 UINT16 Alteration 1The contents of the following indices can be automaticallyaltered by the int
1152 UINT8 Vst reference junction compensation ext / int at thermocouple0: internal1 external53 UINT8 Rad evolving a root0: no1: yes54 UINT16 Fre fina
1280 UINT16 Mask configuration alarm function81 FLP X1- lower alarm limit actual value82 FLP X1+ upper alarm limit actual value83 FLP A1 Hy alarm hys
13150 UINT16 Mask configuration support / single controller151 FLP kp1 amplification heating / continuous152 FLP kp2 amplification cooling153 FLP Tn r
14183 UINT8 Function binary output0: no (no function)1: alarm2: manual / automatic3: feeler break184 UINT8 Effect binary output0: normal1: inverted190
154.2 Error list operating errorsIndex 401: Acknowledged2: Access OK3: Data base not up to date4: Value outside of value range5: Value cannot be descr
164.3 List of the objects for Digital Batch Controller Type 111520 UINT16 Mask process values21 UINT8 Hardware unit22 FLP Actual volume 123 FLP Actual
1746 UINT8 Remaining time in hours47 UINT8 Remaining time in minutes48 UINT8 Remaining time in seconds49 UINT8 Configuration on / off50 UINT8 Error ou
1880 UINT16 Mask configuration 2nd input81 UINT8 Type 2nd input0: input not in use1: frequency2: 0 - 20 mA3: 4 - 20 mA4: 0 - 10 V82 UINT8 Evolving the
19120 UINT16 Mask configuration binary output121 UINT8 Type binary output0: off1: EOB2: delay122 UINT8 Effect of binary output0: low - active1: high -
2Contents1 Block diagram of functions ... 22 Notices concerning use and safety...
20172 UINT8 Effect0: normal1: inverted180 UINT16 Mask configuration language181 UINT8 Language0: German1: English2: French4.4 Error list operating err
215. RS 232 - Protocol5.1 Transmission format8 Bit ASCII1 Startbit1 Stopbit1 Paritybit (if "odd" or "even")The data is transmitted
22During the writing, the value to be written is transmitted in "Wert".During the reading, the value is not included while going out. When c
236 Configuration of the interfacesWhen the interface card (RS 232 or RS 485 / Profibus) has been installed, then appearsin the menu item "Add. M
24Further information concerning the menusModelocal In the local mode, only data from digital units can be requested through the serialinterface. Exte
Operating Instructions 0507/02_EU-EN_00000000Steuer- und RegeltechnikChristian-Bürkert-Str. 13-1774653 IngelfingenTelefon (0 79 40) 10-111Telefax (0 7
31 Block diagram of functionsDriver RS 232 Driver RS 485CPU 80C51FQAOT-PROM 64 KbitRAM 32 Kbitgalvanic separationDCDCClock 12/16 MHzInterface card RS
42 Notices concerning use and safetyIn order to ensure a perfect functioning and a long working life of the interface cardwhen using this card, the us
53 System description3.1 IntroductionThe Digital Industrial Controller 1110 as well as the Digital Batch Controller 1115 can beequipped with a digital
63.3 Connector pin assignment D sub-connector 9 terminal/female 5 9 6 1RS 232 RS 485 / Profibus 2 TxD 3 reception/transmission
74. ProfibusProfibus is standardized according to DIN 19 245.We support the following features:Get OV (long)ReadWrite.FMS features supported are there
830 FLP Xd2 control offset support/single controller31 UINT8 Relay position output relay0: non-active1: activeBit 0 = position relay 1Bit 1 = position
938 UINT8 Controller errorsx x x x x x x x0 : EEPROM-data configuration OK1 : EEPROM-data configuration defect0 : EEPROM-data parametration OK1 : EEPR