11.8. Programming Data
The control heads have been configured as AS interface version with an extended address range (A/B slaves) for
62 slaves or optionally as an AS interface version for 31 slaves.
A change between the two configurations in the control head is only possibly by exchanging the elec-
tronic PCB!
If one control head is replaced with another control head having a different configuration in the AS interface
field bus system (e.g. AS interface version 62 slaves (A/B-Slave) to replace a device with AS interface version
31 slaves), a configuration error will be generated at the master due to the different ID codes!
In this case (intentional replacement), the current configuration must be reprojected in the AS interface
master. Please read the operating instructions of the used AS interface master!
Programming Data Table:
Programming Data for 62 Slaves
AS interface - Device for A/B slave
addressing (default device)
Programming Data for 31 Slaves
AS Interface (optional)
I/O configuration 7 hex (4 inputs / 4 outputs)
See the Bit Configuration Table:
7 hex (4 inputs / 4 outputs)
See the Bit Configuration Table:
ID code A hex F hex
Extended ID code 1 7 hex (F hex)
Extended ID code 2 E hex (F hex)
Profile S-7. A.E S-7. F.F
Bit Configuration Table:
Data bit D3 D2 D1 D0
Input External initiator S4 Position 3 Position 2 Position 1
Output not used Solenoid valve 3 Solenoid valve 2 Solenoid valve 1
Parameter bit P3 P2 P1 P0
Output not used not used not used not used