Calculation Examples:
Example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):
P
Slave
= P
El
+ 1 x P
Valve-On
+ 2 x P
Valve
+ 1 x P
LED
4.5 W = 1.0 W + 1 x 0.9 W + 2 x 0.8 W + 1 x 1.0 W
or
I
Slave
= I
El
+ 1 x I
Valve-On
+ 2 x I
Valve
+ 1 x I
LED
148 mA = 33 mA + 1 x 30 mA + 2 x 26 mA + 1 x 33 mA
Example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):
P
Slave
= P
El
+ 3 x P
Valve
+ 1 x P
LED
4.4 W = 1.0 W + 3 x 0.8 W + 1 x 1.0 W
or
I
Slave
= I
El
+ 3 x I
Valve
+ 1 x I
LED
144 mA = 33 mA + 3 x 26 mA + 1 x 33 mA
When using an external initiator, its power requirement should be added.
Safety instructions11.6.
DANGER!
Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!
Opening the hood or the housing in an explosive atmosphere is only allowed in the isolated state!•
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the Teach-In procedure in a non-explosive atmosphere) switch off •
the power supply and secure it to prevent restarting!
Observe applicable accident prevention and safety regulations for electrical equipment!•
Risk of injury from improper installation!
Installation may be carried out by authorized technicians only and with the appropriate tools!•
Risk of injury from unintentional activation of the system and an uncontrolled restart!
Secure system from unintentional activation.•
Following installation, ensure a controlled restart.•