8 REPAIR WORK
8.1 Faults
ERROR MESSAGES
Message Cause Effect
PFo
Sensor defective or not
connected
Alarm relay ON; control circuit
according to So1
PFc Sensor short-circuit
Alarm relay ON; control circuit
according to So1
HA High temperature alarm
Alarm relay ON; outputs remain
unchanged
LA Low temperature alarm
Alarm relay ON; outputs remain
unchanged
EAL Digital input alarm Outputs remain unchanged
BAL Serious digital alarm All control outputs deactivated
STATUS OF THE ALARM RELAY
Device status AS = CL AS = OP
Device without power 4 - 6 closed 4 - 6 closed
Normal operation 4 - 6 closed 4 - 6 open
Alarm situation during
operation
4 - 6 open 4 - 6 closed
ACKNOWEDGING ERRORS VIA THE KEYBOARD
Press any button.
The Alarm message remains on the display as long as the alarm conditions
are present. The device then switches to normal operation.
AUTOMATIC ACKNOWLEDGEMENT OF THE ERROR
Message
PFo and PFc -
Room sensor error
After approx. 30 seconds or once the error has been cleared, the
message will be acknowledged automatically. Check the connections
before any replacement of the sensor.
Messages
HA/LA -
High/Low temperature alarm
After a few seconds or once the error has been cleared, the message will
be acknowledged automatically.
External alarms
EAL
and
BAL
are acknowledged after deactivation of the
digital input.