Burkert Type TAT002 Bedienungsanleitung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 64
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
0911 - 11
english
HEATING
Parameter S1C = in; The value HY has been preset to 2 K in the factory.
If the temperature falls below the value SET-HY, the controller output will be
switched on and will be switched off again when SET is exceeded.
2.5 Controlling the loads
CONTROLLER OUTPUT
The control is dependent on the measured temperature (= sensor
temperature). Program the control direction (heating or cooling) with the
parameter S1C.
S1C = dir Cooling SET = Set-value
S1C = in Heating Hy = Switch hysterisis
COOLING
Parameter S1C = dir; The value HY has been preset to 2 K in the factory.
If the temperature exceeds the value SET + HY, the compressor will be
switched on and will be switched off again when the temperature is below SET.
ON
t
t
temperature
SET
SET-HY
heat
t
temperature
compressor
SET
SET+HY
ON
t
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 63 64

Kommentare zu diesen Handbüchern

Keine Kommentare