Burkert Type 8111 Bedienungsanleitung Seite 19

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 112
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 18
6 Set up
6.1 General information
The gures in brackets refer to the following illustrations.
The switching condition of the electronics can be checked with closed
housing cover (control lamp). In the basic setting, products with a
density > 0.7 g/cm³ (0.025 lbs/in³) can be detected. For products with
lower density, the sw itch must be set to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will nd the following indicating and
adjustment elements:
l Signal lamp (1)
l DIL switch for characteristics reversal - min./max. (2)
l DIL switch for sensitivity adjustment (3)
l Simulation key (4)
Note:
For test purposes, immerse the tuning fork of LEVEL SWITCH 8111
always in liquids. Do not test the function of LEVEL SWITCH 8111 with
your hand. This can damage the sensor.
6.2 Adjustment elements
1
5
2
3
4
Fig. 10: Oscillator SWE60N - NAMUR output
1 Signal lamp (LED)
2 DIL switch for characteristics reversal
3 DIL switch for sensitivity adjustment
4 Simulation key
5 EMC lter element
Func
tion/Conguration
LEVEL SWITCH 8111 with NAMUR output 19
6 Set up
32048-EN-120418
Seitenansicht 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 111 112