With the mode adjustment (A/B) you can change the switching
condition of the relay. You can set the required mode according to the
"Function chart" (A - max. detection or overow protection, B - min.
detection or dry run protection).
With this DIL switch (3) you can set the switching point to liquids
having a density between 0.5 and 0.7 g/cm³ (0.018 and 0.025 lbs/in³).
With the basic setting, liquids with a density of > 0.7 g/cm³ (0.025 lbs /
in³) can be detected. In liquids with lower density, you must set the
switch to > 0.5 g/cm³ (0.018 lbs/in³). The specications for the position
of the switching point relate to water - density value 1 g/cm³ (0.036 lbs/
in³). In products with a dierent density, the switching point will shift in
the direction of the housing or tuning fork end depending on the
density and type of installation.
Note:
Keep in mind that foams with a density > 0.45 g/cm³ (0.016 lbs/in³) are
detected by the sensor. This can cause faulty switchings particulary
when used as dry run protection system.
6.3 Function chart
The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.
Level Switching status Control lamp
Mode A
Overow protection
53
4
(8)(6) (7)
Relay energized Green
Mode A
Overow protection
53
4
(8)(6) (7)
Relay deenergized Red
Mode B
Dry run protection
53
4
(8)(6) (7)
Relay energized Green
Mode B
Dry run protection
53
4
(8)(6) (7)
Relay deenergized Red
Mode
adjustment (2)
Sen
sitivity adjustment
(3)
LEVEL SWITCH 8112 - Relay (DPDT) 21
6 Set up
32050-EN-120418