Operating and functions
8.7.1. Adjusting the current output
This parameter makes it possible to adjust the value of the current transmitted on the analogue output.
CAL AO1 OFFsEt
CALiB. 0
OF= 4.05
The device generates a 4 mA current.
Measure the current given on the 4-20 mA output using a multimeter.
Enter the value displayed by the multimeter. The permitted offset range is 3 to
5 mA.
Confirm.
sPAN
sP= 19.95
The device generates a 20 mA current.
Measure the current given on the 4-20 mA output using a multimeter.
Enter the value displayed by the multimeter. The permitted span range is 18,50 to
21,50 mA.
Confirm.
VALiD N/Y
Confirm the entered values or not.
Fig. 55: Diagram of the "CAL AO1" of the Test menu
If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press
ENTER
to save the settings or not and go back to the Process level.